The volt-ampere (SI symbol: VA, sometimes V⋅A or V A) is the unit of measurement for apparent power in an electrical circuit. It is the product of the root mean square voltage (in volts) and the root mean square current (in amperes).Ciletti, M. D., Irwin, J. D., Kraus, A. D., Balabanian, N., Bickard, T. A., and Chan, S. P. (1993). Linear circuit analysis. In Electrical Engineering Handbook, edited by R. C. Dorf. Boca Raton: CRC Press. (pp.82–87) Volt-amperes are usually used for analyzing alternating current (AC) circuits. In direct current (DC) circuits, this product is equal to the real power, measured in . IEEE 100 : the authoritative dictionary of IEEE standards terms.-7th ed. , page 14 The volt-ampere is dimensionally equivalent to the watt: in SI units, 1 V⋅A = 1 W. VA rating is most used for generators and transformers, and other power handling equipment, where loads may be reactive (inductive or capacitive).
For alternating current, both the voltage and current are oscillating. Instantaneous power is still the product of instantaneous current and instantaneous voltage, but if both of those are ideal sine waves driving a purely resistive load (like an incandescent light bulb), average power becomes (with subscripts designating average (av), peak amplitude (pk) and root mean square (rms)):
More generally, when voltage and current are not in phase, these products no longer represent average power but a new apparent power, measured in volt-amperes:
Some devices, including uninterruptible power supplies (UPSs), have ratings both for maximum volt-amperes and maximum watts. A common SI prefix derived unit is "kilovolt-ampere" (symbol kVA). The VA rating is limited by the maximum permissible current, and the watt rating by the power-handling capacity of the device. When a UPS powers equipment which presents a reactive load with a low power factor, neither limit may safely be exceeded. Watt Ratings Differs from Volt Amp Ratings APC For example, a (large) UPS system rated to deliver 400,000 volt-amperes (400 kVA) at 220 volts can deliver a current of 1818 amperes (these are RMS values).
VA ratings are also often used for transformers; maximum output current is then VA rating divided by nominal output voltage. Transformers with the same sized core usually have the same VA rating.
The convention of using the volt-ampere to distinguish apparent power from real power is allowed by the SI standard.
Special instruments called varmeters are available to measure the reactive power in a circuit.
The unit "var" is allowed by the International System of Units (SI) even though the unit var is representative of a form of power. Per EU directive 80/181/EEC (the "metric directive"), the correct symbol is lower-case "var", Council Directive on units of measurements 80/181/EEC Chapter 1.2.3., p. 6: "Special names for the unit of power: the name volt–ampere (symbol ‘VA’) when it is used to express the apparent power of alternating electric current, and var (symbol ‘var’) when it is used to express reactive electric power." although the spellings "Var" and "VAr" are commonly seen, and "VAR" is widely used throughout the power industry.
|
|